Pending approvalDrafted work order for P-12 bearing replacement
Timeline
- 02:14:08Anomaly detected on P-12Vibration 4.6 mm/s (threshold 4.5)
- 02:14:30Pulled 72h trendquery_tags→ Linear rise 2.1 → 4.6 mm/s
- 02:15:12Spectral analysisInner-race bearing wear signature
- 02:16:04Failure projection4–6 days to critical threshold
- 02:16:48Looked up bearing partknowledge_search→ SKF-6205-2RS from manual
- 02:17:24Checked stockcall_inventory_api→ 14 units on hand
- 02:18:06Found maintenance windowquery_schedule→ Thu 02:00–04:00 available
- 02:19:42Drafted work orderWO-4521 created in CMMS draft state
- 02:21:18Submitted for approval→ Pending Sam Rivera